timohei.net / My Courses / TL110103 PLC Control 3 cu / Excercise: Valve Control /
PLC I/O: Inputs

 
Venttiilin ohjauskotelo = Valve Local
Control Panel
K = Closed
A = Opened
OHJAUS = CONTROL
LIIKKUU = MOVING
VALVONTA-AIKA = DISCREPANCY  

K = Closed
A = Opened
OHJAUS = CONTROL
LIIKKUU = MOVING
VALVONTA-AIKA = DISCREPANCY
- Control Switch "Closed/Opened"
 - A turning switch in the Local Panel
 - Activates driving of the valve to open or closed position
 - Input switch in open position (0) -> the valve is closed
 - Input switch in closed position (1) -> the valve is opened
 - Limit Switch "Closed"
 - A limit switch at the valve
 - the switch is closed only when the valve is fully closed
 - both limit switches are open when the valve is in an intermediate position
 - Limit Switch "Opened"
 - A limit switch at the valve
 - the switch is closed only when the valve is fully opened
 - both limit switches are open when the valve is in an intermediate position
 
Updated 14.3.2007
© Timo Heikkinen | timo piste heikkinen at oamk piste fi